This is UL924-certified Emergency Lighting Bypass/Shunt Relay. We specifically designed this component to ensure the reliable operation of emergency lighting systems. It is also an essential component of safety and compliance in emergency situations thanks to its robust capacity and compatibility with multiple power sources.

Description

・Emergency lighting load control relays.
・ALCR Automatic Load Control Relay
・Conforms To UL STD 924.
・Operating Voltage: 100 Vac to 277Vac / 140Vdc to 390Vdc.
・Operating Temperature: -25°C to +70°C.
・Built-in DALI PSU, 15V / 200mA . Signal Relay Specification
・One (1) SPDT Continuous Duty Coil.
・1 Million Cycles Minimum Mechanical Lifetime.
・Operate Time: 3mS.
・Maximum Switching Load Voltage:250Vac / 30Vdc.
・Maximum Switching Load Current:1A.

Additional information

Dimming

0-10V/ELV

Voltage

120v-2777v

Style